Refrigeration Research - 3810 - Vertical Suction Accumulator, 1-5/8" O.D.

Item: RER3810
MFG: 3810
loading availability
Loading price
/ EA

Description

The ORIGINAL, TIME TESTED SUCTION ACCUMULATOR
- - THE COMPLETE LINE - -
For Exact Selection


Air conditioning, heat pump, truck refrigeration and many other applications require intermittent
operation of the refrigeration compressor. Especially in remote applications, the suction line may trap or
hold quantities of liquid which are suddenly dumped into the compressor as it starts up. This is frequently
the cause of broken valves, pistons, broken or bent connecting rods, blown gaskets and bearing washout.

Proper installation of the Refrigeration Research suction accumulator in the suction line, just before the compressor, eliminates damage. If correctly sized, relatively large quantities of liquid refrigerant may return through the suction line and the suction accumulator prevents damage to the compressor. Liquid is temporarily held in the suction accumulator and metered back to the compressor along with any oil, at a controlled rate, through the metering orifice. Therefore, damage to the compressor is prevented and the compressor immediately and quietly goes to work.

THE ORIGINAL, YET IMPROVED, SUCTION ACCUMULATOR BY REFRIGERATION RESEARCH PROVIDES ALL OF THE IMPORTANT FEATURES.
  1. Exclusive (patented) inlet deflector for improved performance. Deflector permits tangential entry of fluid.
  2. Marking of inlet with a metal plate is an exclusive feature and helps prevent errors in hook up.
  3. All Refrigeration Research suction accumulators of 4” through 6” diameter have fusible plugs included and installed to comply with latest and requirements.
  4. Copper nipples are standard on vertical and models.
  5. Controlled hydrogen copper brazing process provides the ultimate in cleanliness and uniform strength.
  6. All Refrigeration Research suction accumulators are and listed or built to ASME code, CE documentation also available. Suction accumulators by Refrigeration Research have been field proven in hundreds of thousands of installations.
SELECTION OF SUCTION ACCUMULATOR - The suction accumulator should not necessarily be selected to have the same size inlet and outlet as the compressor suction line. It is more important to select the suction accumulator well within the limits of (1) pressure drop, (2) oil return as shown on the following page and (3) total amount of charge to be held.

The actual refrigerant holding capacity needed for a suction accumulator is governed by the requirements of the particular application. There is a great variation in refrigeration systems and this must be considered. Where possible the capacity selected should be checked by actual test. Normally the accumulator should not be sized for less than 50% of the total system capacity. If in doubt, consult the compressor manufacturer. Steel nipples are available on special order.

California residents: see Proposition 65 Warning

Features and Specification

Weight 22
Brand Refrigeration Research
Composition Steel
Connection Size 1 5/8"
Connection Type Steel
Cubic Measurement 0.625
Height 6
Inlet Connection Size 1-5/8"
Length 30
Outlet Connection Size 1-5/8"
Prop 65 No
Refrigerant Capacity 21 Pounds
UL Listed Yes
UL Recognized No
UOM EA
Width 6
Country of Origin USA